(Created page with " == Abstract == This paper deals with the problem of AC interference on buried metallic pipelines located in proximity of HVAC power lines. A numerical technique for the asse...") |
m (Scipediacontent moved page Draft Content 710016201 to Popoli et al 2019a) |
(No difference)
|
This paper deals with the problem of AC interference on buried metallic pipelines located in proximity of HVAC power lines. A numerical technique for the assessment of the induced electromagnetic variables on the conductors of the right-of-way is introduced and applied to a realistic interference case, involving a non-parallel routing of the pipeline with respect to the power line. The presented approach is then employed to evaluate the efficacy of mitigation measures that can put in place to suitably lower the electromagnetic impact on the considered metallic pipeline. Finally, a dedicated interpolation technique is applied to the gathered data, and it is shown how it can consistently be used to extend the range of applicability of the computed results.
The different versions of the original document can be found in:
Published on 31/12/18
Accepted on 31/12/18
Submitted on 31/12/18
Volume 2019, 2019
DOI: 10.1109/eeeic.2019.8783843
Licence: CC BY-NC-SA license
Are you one of the authors of this document?